
ENVIROMUX-ACVD-515
ENVIROMUX-ACVD-C14
 |

ENVIROMUX-S60VDC
|
- Measurement range: detects voltage from 50 to 250 VAC.
- Measurement indication: Alarm or Normal.
- Sensor type: open/closed contact switch.
- Includes 6-foot 2-wire cable to connect to the ENVIROMUX-SEMS-16.
- Attached 0.9 meter power cord.
- ENVIROMUX-ACVD-515: Standard US 120V 15A NEMA 5-15 plug
- ENVIROMUX-ACVD-C14: Universal 250V IEC C14 socket
- Regulatory approvals: CE, RoHS
|
- Monitors up to two DC voltages: -60VDC ~ 0VDC or 0VDC ~ 60VDC
- Connector: Screw Terminal, 5-position
- Supports CAT5/5e/6 cable up to 305 meters (not included)
- Includes Mounting Hardware
- Regulatory approvals: RoHS
|
ENVIROMUX-ACLM-P12 ENVIROMUX-ACLM-P8
 |

ENVIROMUX-ACLM-V
|
- Reports AC Voltage, Frequency, Power, and Current to the ENVIROMUX-SEMS-16.
- Monitors Power from one AC inlet to one AC outlet, between 50~250VAC and 47~63Hz.
- Monitors the number of swells, sags, and spikes.
- Includes Relay with configurable disconnect settings: threshold reboot, or manual reboot.
- Outlet Max load rating:
- ENVIROMUX-ACLM-P12 (US/Canada):
12A rated load, 15A maximum.
- ENVIROMUX-ACLM-P8 (Euro/UK):
8A rated load, 10A maximum.
- Capable of measuring current surges to 60A.
- User defined minimum and maximum voltage and power thresholds.
- Capable of detecting user selected spike events with a peak greater than 50V, 250V, 500V, or 1KV.
- Supports CAT5/5e/6 cable up to 305 meters. (not included).
- Regulatory approvals: RoHS
|
- Reports AC Voltage and Frequency to the ENVIROMUX-SEMS-16.
- Monitors AC voltage and frequency on two AC inlets between 50~250VAC and 47~63Hz.
- Monitors the number of swells, sags, and spikes.
- User defined minimum and maximum voltage thresholds.
- Capable of detecting user selected spike events with a peak greater than 50V, 250V, 500V, or 1KV.
- Supports CAT5/5e/6 cable up to 305 meters. (not included).
- Regulatory approvals: RoHS
|

ENVIROMUX-PWR-RLY-15A
ENVIROMUX-PWR-RLY-20A
 |
ENVIROMUX-2W-xx
 |
- Use with ENVIROMUX-SEMS-16 to remotely turn off the power of an AC powered device.
- Remotely reboot non-responsive computer systems.
- Two AC power receptacles.
- Load capacity:
- ENVIROMUX-PWR-RLY-15A: 15A at 120VAC.
- ENVIROMUX-PWR-RLY-20A: 20A at 120VAC.
- Dimensions WxDxH (mm): 96.5x50.8x139.7
- The baseplate is 133 mm square.
- Regulatory approvals: TUV
|
- 2-wire sensor cable.
- Use to connect dry contact sensors to the ENVIROMUX-SEMS-16.
- Available lengths: .9/1.8/3/7.6/15.2/30.5 meters
- Regulatory approvals: RoHS, UL
|